Estimation of the condensation heat transfer coefficient for steam water at low pressure in a coiled double tube condenser integrated to a heat transformer

 

O. Flores, V. Velázquez, M. Meza, H. Horacio, D. Juárez and J. A. Hernández

 

 

  • Experimental heat transfer coefficient for steam water in a condenser coil.

  • An equation is proposed to the heat transfer coefficient for steam water in a condenser coil.

  • Plot Wilson method is applied to estimate the heat transfer coefficient.

  • The proposed equation considers numbers Nu, Re and Pr.

  • Nu=1.6840 Re0.6897 Pr1.5398.